OBIOLimitSwitch (FB)
FUNCTION_BLOCK OBIOLimitSwitch EXTENDS AbbLConC3
A binary output can be switched on/off with respect to a counter value.
- precondition
the respective channel is configured as limit switch, and also a counter channel has to be configured.
Up to 8 limit-switches are possible.
Note
This block should just be called once per cycle otherwise inconsistent values could be send to PRU, if send twice in short time.
- InOut:
Scope
Name
Type
Initial
Comment
Inherited from
Input
EnableBOOLFALSE
A rising edge (Enable = TRUE) starts the operation, the output Busy goes to TRUE. All other inputs are read and considered continuously. Execution will continue forever until a falling edge (Enable = FALSE) aborts the operation. During Aborting the Busy is still TRUE. Afterward all outputs are reset.
AbbLConC3
Output
BusyBOOLFALSE
Operation is running (while output Error is FALSE)
AbbLConC3
ErrorBOOLFALSE
Operation is stopped with error (while output Busy is FALSE). This output is TRUE for at least one cycle or until Enable is set to FALSE. The output ErrorID gives more details about the error.
AbbLConC3
Input
ChannelBYTE0..7
SignalBOOLSelects whether corresponding output should be high or low when counter is between UpperLimitOn and LowerLimitOn
ManualModeBOOLTRUE: related output will be switched to ManualModeValue (TRUE or FALSE)
ManualModeValueBOOLUpperLimitOnUDINTUpper limit UpperLimitOn > LowerLimitOn
LowerLimitOnUDINTLower limit LowerLimitOn < UpperLimitOn
Inout
CounterOBIOBaseCounterlink the block to the counter which will be used to trigger the output
Output
ErrorIDError Code
StateBOOLreflects the state of the binary output related to LimitSwitch