The system data of AC500 and S500 are applicable to the standard version.⮫ “System data AC500”
The system data of AC500-XC are applicable to the XC version.⮫ “System data AC500-XC”
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Parameter |
Value |
---|---|
Connection of the supply voltage 24 V DC at the terminal base of the processor module |
Removable 5-pin terminal block spring type |
Max. current consumption from 24 V DC |
TB5600: 0.3 A 1) TB5610: 0.4 A 1) TB5620: 0.5 A 1) TB5640: 0.65 A 1) TB5660: 0.8 A 1) |
Melting integral of a fuse at 24 V DC |
Min. 1 A²s 2) |
Peak inrush current from 24 V DC |
55 A 2) |
Number of slots for processor modules |
1 (on all terminal bases) |
Processor module interfaces at TB56xx |
I/O bus, ETH1, ETH2, CAN, COM1 |
Net weight (terminal base without processor module) |
TB5600: 155 g TB5610: 180 g TB5620: 210 g TB5640: 260 g TB5660: 310 g |
Mounting position |
Horizontal or vertical |
1) Including processor modules, communication modules and I/O bus supply.
2) The inrush current and the melting integral depends on the internal power supply of the processor module and the number and type of communication modules and I/O modules connected to the I/O bus.
Processor module |
PM5630 |
PM5650 |
PM5670 |
PM5675 |
---|---|---|---|---|
TB5600-2ETH |
0 slot |
0 slot |
0 slot |
0 slot |
TB5610-2ETH |
1 slot |
1 slot |
1 slot |
1 slot |
TB5620-2ETH |
2 slots |
2 slots |
2 slots |
2 slots |
TB5640-2ETH |
- |
4 slots |
4 slots |
4 slots |
TB5660-2ETH |
- |
- |
6 slots 1) |
6 slots 1) |
Remarks: The slots can be used for connecting communication modules or AC500-S modules. Note that only one AC500-S module can be connected at one terminal base. 1) PM567x must have an index ≥ C0. |