Technical dataPermalink

This is the web edition of the original ‎⮫ AC500-S safety user manual, version 1.3.2. This web edition is provided for quick reference only. The original safety user manual must be used to meet functional safety application requirements.

NOTICE

NOTICE
NOTICE
NOTICE

NOTICE

NOTICE

DI581-S-XC version is available for usage in extreme environmental conditions.

Additional technical data is available in ABB PLC catalog at ‎⮫ www.abb.com/plc.

Process supply voltage UP

Data

Value

Unit

Connections terminals 1.8 ... 4.8 (UP)

+24

V

Connections terminals 1.9 ... 4.9 (ZP)

0

V

Rated value (-15 %, +20 %, without ripple)

24

V DC

Max. ripple

5

%

Protection against reversed voltage

Yes

 

Rated protection fuse for UP (fast)

10

A

Electrical isolation

per module

 

Mechanisms in which I/Os are processed

periodically refreshed

 

Current consumption from UP at normal operation with + 24 V DC (for module electronics)

0.18

A

Inrush current from UP at 30 V (at power up)

0.1

A2s

Inrush current from UP at 24 V (at power up)

0.06

A2s

NOTICE

NOTICE
NOTICE
NOTICE

NOTICE

NOTICE

All DI581-S channels (including test pulse outputs) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 V DC.

Mounting position

Horizontal or vertical with derating (maximal operating temperature reduced to +40 °C)

Cooling

The natural convection cooling must not be hindered by cable ducts or other parts in the control cabinet.

Allowed interruptions of power supply, according to EN 61131-2

Data

Value

Unit

DC supply interruptions

< 10

ms

Time between 2 DC supply interruptions, PS2

> 1

s

Environmental conditions

Data

Value

Unit

Operating temperature*

0 ... +60

°C

Storage temperature

-40 ... +85

°C

Transport temperature

-40 ... +85

°C

Humidity without condensation

max. 95

%

Operating air pressure

> 800

hPa

Storage air pressure

> 660

hPa

Operating altitude

< 2000

m above sea level

Storage altitude

< 3500

m above sea level

* Extended temperature ranges (below 0 °C and above +60 °C) can be supported in special versions of DI581-S.

Creepage distances and clearances

The creepage distances and clearances meet the overvoltage category II, pollution degree 2.

Power supply units

For the supply of modules, power supply units according to PELV/SELV specifications must be used.

Electromagnetic compatibility

For information on electromagnetic compatibility refer to the latest TÜV SÜD Report⮫ [1].

Mechanical properties

Data

Value

Unit

Degree of protection of the PLC system

IP 20 (with all modules, option boards and terminals plugged in and with all covers closed)

 

Housing

according to UL 94

 

Vibration resistance acc. to EN 61131-2 (all three axes), continuous 3.5 mm

2 ... 15

Hz

Vibration resistance acc. to EN 61131-2 (all three axes), continuous 1 g *

15 ...150

Hz

Shock test (all three axes), 11 ms half-sinusoidal

15

g

MTBF

102

years

* Higher values on request

Self-test and diagnostic functions

Start-up and runtime tests: Program flow control, RAM, CPU, cross-talk, stuck-at-1, etc.

Dimensions, weight

Data

Value

Unit

W x H x D

67.5 x 76 x 62

mm

Weight

~ 130

g

Certifications