The default value of the boot-parameter Communication Schema
is the balanced priority for communication via communication modules (CMs) and onboard
Ethernet communication.

The highest IEC task priority 0 should be used for high prior functions in the PLC with short execution time.
The communication modules interrupts (CM5xx), the I/O bus, the IEC scheduler observer task and the CAA event task are processed with higher priority than all user IEC tasks.
Ethernet runs on non-real-time priority.
The default setting of the priorities is suitable for most applications and corresponds to the settings in the firmware versions 3.4.0 and before.