fbIEC61850_Subscriber (FB)

FUNCTION_BLOCK fbIEC61850_Subscriber

InOut:

Scope

Name

Type

Comment

Input

paObjList

POINTER TO ARRAY [0..16#FFFF] OF tyIEC61850_SubsDataPoint

wObjNums

WORD

Nums of Object

Output

dtLastAction

DT

Timestamt, last GOOSE Msg received

xNewMsg

BOOL

New GOOSE Msg received

wRxCounter

WORD

Receive counter

sStatus

STRING(200)

Current status text

xErrorTimeAllowedToLive

BOOL

TimeAllowedToLive parameter will be checked, how long the subscriber wait until this flag will be set if connection lost

xError

BOOL

Indicates if an error in a subcribed message detected

sGoCBRef

tyIEC61850_AT_VisSTRING255

nTimeAllowedToLive

tyIEC61850_AT_INT32

sDatSet

tyIEC61850_AT_VisSTRING255

t

tyIEC61850_AT_TimeStamp

nStNum

tyIEC61850_AT_INT32

nSqNum

tyIEC61850_AT_INT32

xSimulation

tyIEC61850_AT_BOOLEAN

nConfRev

tyIEC61850_AT_INT32

xNdsCom

tyIEC61850_AT_BOOLEAN

nNumDatSetEntries

tyIEC61850_AT_INT32

Methods:

NewMsg

Structure: