Declaration of used variablesPermalink

This is the web edition of the original ‎⮫ AC500-S safety user manual, version 1.3.2. This web edition is provided for quick reference only. The original safety user manual must be used to meet functional safety application requirements.

Table 1157: Inputs

Name

Data type

Description

S1_S_EStopIn

BOOL

Emergency stop button S1

S2_MutingSwitch11

BOOL

Muting sensor S2

S3_MutingSwitch12

BOOL

Muting sensor S3

S4_MutingSwitch21

BOOL

Muting sensor S4

S5_MutingSwitch22

BOOL

Muting sensor S5

S6_S_GuardSwitch

BOOL

Door switch S6 with two contacts

S7_S_AOPD_In

BOOL

OSSD from light curtain S7

K1_EDM

BOOL

Feedback from external device K1 (actuator)

K2_EDM

BOOL

Feedback from external device K2 (actuator)

S9_Reset

BOOL

Reset safety demand by user S9

S0_Reset

BOOL

Reset error by user S0 (derived from functional application)

ApplCtrl1

BOOL

Signal controlling the actuator, enabled by safety loop (derived from functional application)

StartTest_LC1

BOOL

Signal starting test of light curtain S7 (derived from functional application)

ApplMutingEnable1

BOOL

Signal enabling start of the muting sequence (derived from functional application)

Table 1158: Outputs

Name

Data type

Description

S_EDM_Out_K

BOOL

Drives actuator via K1 and K2

S_MutingActive_L1

BOOL

Drives muting lamp L1

S_TestOut_LightCurtain_S8

BOOL

Test output for light curtain S8

Errors

BOOL

Represents all errors of the used FB (connected to functional application)

DiagCodes

WORD

Represents all diagnostic codes of the used FB (connected to functional application)

TestPossible_LC1

BOOL

Indicates to the functional application that an automatic sensor test of the light curtain is possible.

TestExecuted_LC1

BOOL

Indicates to the functional application the successful execution of an automatic sensor test of the light curtain.

Table 1159: Local variables

Name

Data type

Description

S_SafeControl

BOOL

Indicates the status of the safety guards (TRUE = safety enabled)