Additional notes Permalink

This is the web edition of the original ‎⮫ AC500-S safety user manual, version 1.3.2. This web edition is provided for quick reference only. The original safety user manual must be used to meet functional safety application requirements.

In this example, two contacts of the guard switch are connected to a safety input device, which realizes the error detection. The resulting BOOL signal is mapped to the two input channels of the SF_Guard_1.

The diagnostic information retrieval has not been covered in this example. For this, refer to⮫ “Additional notes”. The input parameter Activate for the dynamic FB activation has been set to TRUE. However, in an application, this can be replaced by a variable.

Information about the used function block parameters

Function block

Input

Constant value

Description

SF_EmergencyStop_1

S_StartReset

TRUE

Automatic reset allowed when PES is started

S_AutoReset

FALSE

No automatic reset, user reset/acknowledge necessary

SF_Guard_1

S_StartReset

TRUE

Automatic reset allowed when PES is started

S_AutoReset

FALSE

No automatic reset, user reset/acknowledge necessary

DiscrepancyTime

T#0ms

The discrepancy time between both safety inputs S_GuardSwitchX is not monitored, because they are identical and since the input unit provides one signal of type BOOL from the contactors.

SF_MutingSeq_1

S_StartReset

TRUE

Automatic reset allowed when PES is started

MaxMutingTime

T#30s

The maximum muting time is monitored to be within 30 s

SF_LightCurtain_1

S_StartReset

TRUE

Automatic reset allowed when PES is started

S_AutoReset

FALSE

No automatic reset, user reset/acknowledge necessary

TestTime

T#100ms

The maximum test time is monitored to be within 100 ms

NoExternalTest

TRUE

The external manual sensor test is not supported.

SF_OutControl_1

S_StartReset

FALSE

No automatic reset allowed when PES is started

S_AutoReset

FALSE

No automatic reset, user reset/acknowledge necessary

StaticControl

FALSE

A dynamic change of the signal ApplCtrl1 (rising edge) is required after block activation or a triggered safety function (S_SafeControl = FALSE).

SF_EDM_1

MonitoringTime

T#30ms

The maximum response time of both feedback signals EDM1 and EDM2 are monitored to be within 30 ms.