Requirement: In your project, alarms are defined in alarm groups and they are assigned to an alarm class. The following instructions are based on the example which is described in the ⮫ “Creating an Alarm Management ” chapter.
The alarm banner displays an active alarm in online mode. If there are multiple active alarms, filtering takes place by means of the filter criteria set in the alarm banner (newest for filter criterion "Priority" and most important for filter criterion "Newest"). See the instructions below for adding scroll elements in order to switch the display between multiple alarms.
-
Open the visualization editor.
-
Drag the “Alarm Banner” element from the “Alarm Manager” group to the visualization editor.
The “Alarm Banner” visualization element is visible in the editor.
-
In the “Alarm configuration” / “Alarm groups” property, define the alarm groups that you want to visualize. Click into the value field.
The “Select Alarm Group” dialog opens.
-
Clear the “All” check box and select the “PartsShortage” alarm group. Click the
button to add the group to the selected alarm groups.
-
In the “Alarm configuration” / “Alarm classes” property, define the alarm classes that you want to visualize. Click into the value field.
The “Select Alarm Class” dialog opens.
-
Clear the “All” option and select the “PartsShortage” alarm class. Click the
button to add the alarm class to the selected alarm classes.
-
Set the “Alarm configuration” / “Filter criterion” property to “Newest”.
In online mode, the newest alarm message is always shown.
-
Add an additional column. Click the “Columns” / “Create new” button.
CODESYS adds the “[2]” column to the properties. The “Symbol” column is added to the table.
-
Select the “State” data type for column [2].
The default “State” column heading is shown in the table.
-
In the “Confirmation variable” property, specify the variable
bQuitAlarm
for confirming messages.