WARNING_ID (ENUM)
- TYPE WARNING_ID(
NO_WARNING
Enumeration of the Warning ID, describes the details of each Warning generated by library function blocks.
- Attributes:
qualified_only- InOut:
Name
Initial
Comment
NO_WARNING
0
No warning
DELAYTIME_LONG
-2
Delay time too long compared to temperature gradient TU/TG<0.49 required
RATIO_EXCEEDED
-3
Ratio V1 = TU / TG > maximum value A(iMaxOrd) = A(5), where iMaxOrd = Maximum order of PTn ( n number of PT1(First order elements )connected in series ) model
ADAPTION_CANCELLED
-4
Adaptation cancelled before turning point. Point of inflexion was not reached: use higher step change or use smaller control variable or use SetItg