Technical dataPermalink

This is the web edition of the original ‎⮫ AC500-S safety user manual, version 1.3.2. This web edition is provided for quick reference only. The original safety user manual must be used to meet functional safety application requirements.

Additional technical data is available in ABB PLC catalog at ‎⮫ www.abb.com/plc.

NOTICE

NOTICE
NOTICE
NOTICE

NOTICE

NOTICE

Safety CPU -XC version is available for usage in extreme environmental conditions.

Memory

Data

Value

Unit

User program memory of SM560-S

1

MB

User program memory of SM560-S-FD-1 and SM560-S-FD-4

1.3

MB

User data memory (thereof 120 kB saved)

1

MB

Performance

Data

Value

Unit

Cycle time - binary

0.05

µs/instruction

Cycle time - word

0.06

µs/instruction

Cycle time - floating-point

0.50

µs/instruction

Voltages, according to EN 61131-2

Data

Value

Unit

Process and supply voltage (without ripple)

24 (-15 %, +20 %)

V DC

Absolute limits (including ripple)

19.2 ... 30

V DC

Ripple

< 5

%

Protection against reverse polarity

10

s

DANGER

DANGER
DANGER
DANGER

DANGER

DANGER

Exceeding the permitted process or supply voltage range (< -35 V DC or > +35 V DC) could lead to unrecoverable damage of the system.

Allowed interruptions of power supply, according to EN 61131-2

Data

Value

Unit

DC supply interruptions

< 10

ms

Time between 2 DC supply interruptions, PS2

> 1

s

Environmental conditions

Data

Value

Unit

Operating temperature*

0 ... +60

°C

Storage temperature

-40 ... +85

°C

Transport temperature

-40 ... +85

°C

Humidity without condensation

max. 95

%

Operating air pressure

> 800

hPa

Storage air pressure

> 660

hPa

Operating altitude

< 2000

m above sea level

Storage altitude

< 3500

m above sea level

* Extended temperature ranges (below 0 °C and above +60 °C) can be supported in special versions of the safety CPU.

Creepage distances and clearances

The creepage distances and clearances meet the overvoltage category II, pollution degree 2.

Power supply units

For the supply of modules, power supply units according to PELV/SELV specifications must be used.

Electromagnetic compatibility

For information on electromagnetic compatibility refer to the latest TÜV SÜD Report⮫ [1].

Mechanical properties

Data

Value

Unit

Mounting

horizontal (or vertical with derating (maximal operating temperature reduced to +40 °C))

 

Degree of protection of the PLC system

IP 20 (with all modules, option boards and terminals plugged in and with all covers closed)

 

Housing

according to UL 94

 

Vibration resistance acc. to EN 61131-2 (all three axes), continuous 3.5 mm

2 ... 15

Hz

Vibration resistance acc. to EN 61131-2 (all three axes), continuous 1 g *

15 ... 150

Hz

Shock test (all three axes), 11 ms half-sinusoidal

15

g

MTBF

168

years

* Higher values on request

Self-test and diagnostic functions

Start-up and runtime tests: Program flow control, RAM, CPU, etc.

Dimensions, weight

Data

Value

Unit

W x H x D

28 x 135 x 75

mm

Weight

~ 100

g

Certifications

CE, cUL (further certifications at ‎⮫ www.abb.com/plc)