CM589-PNIO(-4) errorsPermalink

In PLC display the diagnosis messages of “CM589-PNIO” are not shown.

The following diagnosis messages are signaled by “CM589-PNIO”:

Error severity

SubSysteminfo

Additional

Error code

Meaning

Remedy

3

0

0

1000

No communication module or wrong type found.

Plug the correct communication module.

3

0

0

1001

Type of CM589-PNIO not supported.

Exchange the communication module.

3

0

0

1002

Firmware version of CM589-PNIO not supported.

Update firmware of CM589-PNIO.

3

0

0

1003

Identification of communication module failed.

Exchange the communication module or plug the correct communication module.

3

0

0

2000

Watchdog error

 

3

0

0

2001

CM589-PNIO is not communicating.

Check bus connection and configuration.

3

0

0

2002

CM589-PNIO signals communication error.

Check bus connection and configuration.

3

0

0

2003

Starting of CM589-PNIO's protocol stack failed.

Check bus connection and configuration.

3

0

0

2004

Stopping of CM589-PNIO 's protocol stack failed.

 

3

0

0

2005

PLC cannot be set to run due to an error of CM589-PNIO.

Check error log and correct errors.

3

0

0

3000

Configuration error

Check configuration and correct errors.

3

0

0

3001

Configuration version mismatch

Use matching CPU firmware version.

3

0

0

4000

Ethernet link down

Check Ethernet cable connection.

3

0

0

10000

Wrong module is configured.

Check configuration and correct errors.

3

0

0

10001

Correct module is configured but locked by another I/O controller.

Check configuration and correct errors.

3

0

0

10002

Module is configured but not used by I/O controller.

Check configuration and correct errors.

3

Slot/subslot

0

65636

Slot/subslot: No module configured.

Check configuration and correct errors.