ParameterizationPermalink

The module itself does not store configuration data. It receives its parameterization data from the master device of the I/O bus (CPU or communication interface module) during power-up of the system.

Hence, replacing I/O modules is possible without any re-parameterization via software.

If the external power supply voltage via UP/ZP terminals fails, the I/O module loses its configuration data. The whole station has to be switched off and on again to re-configure the module.

Firmware version

Configuration

Firmware version > V2.0.0

The arrangement of the parameter data is performed by Control Builder Plus/ Automation Builder software.

The parameter data directly influences the functionality of modules.

For non-standard applications, it is necessary to adapt the parameters to your system configuration.

Module: Module slot address: Y = 1 ... 10

Module parameters

Table 220: Module parameters

No.

Name

Default value

Internal value

Values in menu

1

Ignore module

Yes

0

Yes

1

No

4

Check supply

On

0

On

1

Off

6

Behaviour of outputs at communication errors

Off

0

Off

1+(n*5)

Last value

Last value 5 s

Last value 10 s

2+(n*5)

n £ 2

Substitute value

Substitute value 5 s

Substitute value 10 s

Channel parameters

Table 221: Channel configuration

No.

Name

Default value

Internal value

Operating modes of the analog inputs, individually configurable

1

Channel configuration

Unused

0

Unused (default)

1

Analog input 0 V ... 10 V

2

Digital input

3

Analog input 0 mA ... 20 mA

4

Analog input 4 mA ... 20 mA

5

Analog input -10 V ... +10 V

8

Analog input Pt100, -50 °C ... +400 °C (2-wire)

9

Analog input Pt100, -50 °C ... +400 °C (3-wire), requires 2 channels *)

10

Analog input 0 ... 10 V via differential inputs, requires 2 channels *)

11

Analog input -10 V ... +10 V via differential inputs, requires 2 channels *)

14

Analog input Pt100, -50 °C ... +70 °C (2-wire)

15

Analog input Pt100, -50 °C ... +70 °C (3-wire), requires 2 channels *)

16

Analog input Pt1000, -50 °C ... +400 °C (2-wire)

17

Analog input Pt1000, -50 °C ... +400 °C (3-wire), requires 2 channels *)

18

Analog input Ni1000, -50 °C ... +150 °C (2-wire)

19

Analog input Ni1000, -50 °C ... +150 °C (3-wire), requires 2 channels *)

2

Channel monitoring

Diagnosis

0

Diagnosis (Plausib, Cut wire, Short circuit)

3

Not used

*) In the operating modes with 3-wire configuration or with differential inputs, two adjacent analog inputs belong together (e.g. the channels 0 and 1). In these cases, both channels are configured in the desired operating mode. The lower address must be the even address (channel 0). The next higher address must be the odd address (channel 1). The converted analog value is available at the higher address (channel 1).