The module itself does not store configuration data. It receives its parameterization data from the master device of the I/O bus (CPU or communication interface module) during power-up of the system.
Hence, replacing I/O modules is possible without any re-parameterization via software.
If the external power supply voltage via UP/ZP terminals fails, the I/O module loses its configuration data. The whole station has to be switched off and on again to re-configure the module.
|
Firmware version |
Configuration |
|---|---|
|
Firmware version > V2.0.0 |
The arrangement of the parameter data is performed by Control Builder Plus/ Automation Builder software. |
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configuration.
Module: Module slot address: Y = 1 ... 10
Module parameters
|
No. |
Name |
Default value |
Internal value |
Values in menu |
|---|---|---|---|---|
|
1 |
Ignore module |
Yes |
0 |
Yes |
|
1 |
No |
|||
|
4 |
Check supply |
On |
0 |
On |
|
1 |
Off |
|||
|
6 |
Behaviour of outputs at communication errors |
Off |
0 |
Off |
|
1+(n*5) |
Last value |
|||
|
Last value 5 s |
||||
|
Last value 10 s |
||||
|
2+(n*5) n £ 2 |
Substitute value |
|||
|
Substitute value 5 s |
||||
|
Substitute value 10 s |
Channel parameters
|
No. |
Name |
Default value |
Internal value |
Operating modes of the analog inputs, individually configurable |
|---|---|---|---|---|
|
1 |
Channel configuration |
Unused |
0 |
Unused (default) |
|
1 |
Analog input 0 V ... 10 V |
|||
|
2 |
Digital input |
|||
|
3 |
Analog input 0 mA ... 20 mA |
|||
|
4 |
Analog input 4 mA ... 20 mA |
|||
|
5 |
Analog input -10 V ... +10 V |
|||
|
8 |
Analog input Pt100, -50 °C ... +400 °C (2-wire) |
|||
|
9 |
Analog input Pt100, -50 °C ... +400 °C (3-wire), requires 2 channels *) |
|||
|
10 |
Analog input 0 ... 10 V via differential inputs, requires 2 channels *) |
|||
|
11 |
Analog input -10 V ... +10 V via differential inputs, requires 2 channels *) |
|||
|
14 |
Analog input Pt100, -50 °C ... +70 °C (2-wire) |
|||
|
15 |
Analog input Pt100, -50 °C ... +70 °C (3-wire), requires 2 channels *) |
|||
|
16 |
Analog input Pt1000, -50 °C ... +400 °C (2-wire) |
|||
|
17 |
Analog input Pt1000, -50 °C ... +400 °C (3-wire), requires 2 channels *) |
|||
|
18 |
Analog input Ni1000, -50 °C ... +150 °C (2-wire) |
|||
|
19 |
Analog input Ni1000, -50 °C ... +150 °C (3-wire), requires 2 channels *) |
|||
|
2 |
Channel monitoring |
Diagnosis |
0 |
Diagnosis (Plausib, Cut wire, Short circuit) |
|
3 |
Not used |
|||
|
*) In the operating modes with 3-wire configuration or with differential inputs, two adjacent analog inputs belong together (e.g. the channels 0 and 1). In these cases, both channels are configured in the desired operating mode. The lower address must be the even address (channel 0). The next higher address must be the odd address (channel 1). The converted analog value is available at the higher address (channel 1). |
||||