The PROFINET state is shown by the state LEDs.
LED |
Color |
State |
Description |
|
---|---|---|---|---|
![]() |
PWR |
Green |
On |
Power supply available |
Blinking |
--- |
|||
Off |
Power supply not available or defective hardware |
|||
RDY |
Yellow |
On |
Boot procedure |
|
Blinking |
Boot failure |
|||
Off |
--- |
|||
RUN |
Green |
On |
Communication module is operational |
|
Blinking |
--- |
|||
Off |
Communication module is not operational |
|||
STA1 |
Red |
On |
Diagnosis alarm reported. At least one device is having a diagnosis alarm. In incorporation with STA2 PNIO: License fault. |
|
Blinking |
System error |
|||
Off |
No system error |
|||
STA2 |
Red |
On |
No connection; in incorporation with STA1 PNIO: license fault |
|
Blinking |
Configuration fault: some configured I/O modules are not connected |
|||
Off |
No bus error, communication is running |
|||
STA1 |
Yellow |
Blinking (synchronously) |
No production data available, no bus communication possible. |
|
STA2 |
Yellow |
|||
LED state during firmware update |
STA1 |
Green |
Blinking (synchronously) |
Firmware file transfers during communication module firmware update. |
STA2 |
Red |
|||
STA1 |
Green |
Blinking (alternately) |
Communication module writes the firmware file to the internal flash. Do not power off the PLC! |
|
STA2 |
Red |
The RJ45 Ethernet connector contains two LEDs showing the current Ethernet port connection state.
LED |
Color |
State |
Description |
|
---|---|---|---|---|
![]() |
PNIO1 LED "Link" |
Green |
On |
Ethernet connection established |
Off |
No Ethernet connection |
|||
PNIO1 LED "RX/TX" |
Yellow |
On |
--- |
|
Blinking |
PROFINET device sends/receives frames |
|||
Off |
--- |
|||
PNIO2 LED "Link" |
Green |
On |
Ethernet connection established |
|
Off |
No Ethernet connection |
|||
PNIO2 LED "RX/TX" |
Yellow |
On |
--- |
|
Blinking |
PROFINET device sends/receives frames |
|||
Off |
--- |