Edition 1 of IEC 61850 is supported only.
-
MMS server only.
-
Data sets for MMS and GOOSE reporting: Max. 20 data sets with max 50 entries each.
-
MMS reporting: Max. 5 MMS clients.
-
GOOSE Subscriber: Max. 50 Ethernet frames per cycle.
If this is not sufficient, the workaround is to reduce the cycle time.
-
Not possible to have 2 or more IEC 61850 server in one Automation Builder project.
Workaround: Create 2 or more projects.
-
Only one logical device per IEC 61850 server.
-
Only one report per data set.
-
Automation Builder is an IED Configurator but no system configurator tool as defined in IEC 61850-6. It cannot export .ssd or .scd files.